Chiller VT.ZUCH-1

Chiller VT.ZUCH-1

Cooling Unit VT.ZUCH-1 is intended to use in closed (liquid circulation) cooling systems. It is mainly used in the machines cooling systems and other equipment working in underground excavations, including potentially explosive atmospheres. Cooling aggregate, by its connection into cooling modules of various types of mechanical devices (e.g. electric motors, hydraulic coolers, mechanical transmissions), enables efficient heat dissipation to the atmosphere. The aggregate can also be used wherever it is needed with assurance that is used in accordance to this manual and in correlation with technical parameters and with keeping required work conditions.

Technical specification
Nominal coolant flow rate (medium) 58 l/min
Nominal working pressure of the coolant (medium) 4,8 bar
Cooling medium water or an oil-water emulsion
The cooling method of medium ventilated by air from a radial fan water-air type cooler
Theoretical cooling capacity 20 kW
Airflow in the cooling system 1,4m3/s
Permissible operating temperature of the medium - power suppl 35°C (or different, depending on the cooling device)
Permissible operating temperature - return 60°C
Water tank capacity 130 l
Electric motor type dSKg 160L-4EP (or other approved motor allowed to work in underground mines in accordance with electrical section)
Installed power 4,0 kW
Rotation speed ~ 1435 rpm
Power supply 500/1000 V
Water pump type SKA 4.03.1.1010.1
Nominal capacity 58 l/min
Maximum capacity 75 l/min
Dimensions H. 1400mm W. 1030mm L. 2150mm
Weight (without the cooling medium) 780 kg